The VX-200SZ-2 is an audio signal output module of the VX-2000 system with speaker line impedance detection. This module is to be mounted in the VX-2000SF Surveillance Frame and detects speaker line short circuits, open circuits by comparing impedance readings, and ground fault. Since the module is equipped with 2 speaker outputs (A and B), broadcasts can be maintained even if one of the two outputs fails. Failures are indicated by the LED on the panel.
Power Source | Supplied from VX-2000SF |
---|---|
Current Consumption | Under 170 mA |
Power Amplifier Link | RJ45 female connector for connecting the VP-2064, VP-2122, VP-2241, VP-2421 Power Amplifier. Twisted-pair straight cable (TIA/EIA-568A standard) |
External Attenuator Control Output | Plug-in screw connector, relay, no-voltage make contact output, transfer type, withstand voltage: 30 V DC, 250 V AC, contact current: Under 7 A (DC), under 7 A (AC) Applicable cable diameter: AWG 24 - AWG 16 |
Speaker Output | 2 outputs (A, B), plug-in screw connector Applicable cable diameter: AWG 24 - AWG 16 |
Power Amplifier Input | Plug-in screw connector for connecting the VP-2064, VP-2122, VP-2241, VP-2421 Power Amplifier. Applicable cable diameter: AWG 24 - AWG 16 |
Fault Detection System | Short circuit, open circuit (impedance detection method), ground fault |
Finish | Panel: Surface-treated steel plate |
Dimensions | 30.5 (W) × 132.6 (H) × 290.3 (D) mm |
Weight | 335 g |
Accessory | Plug-in screw terminal……1 |
Option | Equaliser card: VX-200SE |
Applicable Model | VX-2000SF |